PRODUCTS

Data Center Ceiling Grids

Gordon Grid Pro™

Gordon Grid Pro™ offers enhanced structural strength through advanced profile geometry and engineered stiffener placement. It is designed to support overhead cable and power distribution, wall systems and hot/cold aisle containment barriers.

This next-generation structural ceiling system for data centers is available in imperial dimensions for North America and metric dimensions for the EMEA region.

Gordon Grid Pro™ structural profile

Metric — EMEA

Gordon Grid Pro™ metric profile cross-section
Profile cross-section
Mid-span loading diagram
Mid-span loading diagram

Main runner T-section spacing

Hanger spacing

Deflection

Maximum static point load at mid-span

Maximum linear load at specified deflection

1200 mm

1200 mm

L/360 (3.33 mm)

168 kg

224 kg/m

1200 mm

1200 mm

L/180 (6.67 mm)

336 kg

448 kg/m

Imperial — North America

Gordon Grid Pro™ imperial profile cross-section
Profile cross-section
Mid-span loading diagram
Mid-span loading diagram

Main runner T-section spacing

Hanger spacing

Deflection

Maximum static point load at mid-span

Maximum linear load at specified deflection

48″

48″

L/360 (.133″)

357 lbs

143 lbs/ft

48″

48″

L/180 (.266″)

714 lbs

286 lbs/ft

Back to Gordon systems